KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
Overview:
Wiring
RS-485 Network
COM1 terminals A and B are used.
The A and B naming convention may differ across
manufacturers.
Refer to individual wiring/installation pages in this
manual.
A=(+) non-inverting
B=(—) inverting
Termination and Bias
 This device does not have a termination
resistor installed
 There are two 4.7kohm pull up/down
resistors located on the lines to maintain
bias.
LED Operation
LED2 will blink every time a Modbus request is
seen on the network
Modbus Information
Modbus Communication
Configuration Settings
The gateway is a Modbus slave and all
communication has to be initiated by a master.
To set up successful communication with the
gateway all connection parameters have to be
set correctly to the following: 9600 8-N-1 RTU.
Mode RTU
Baud Rate 9600bps
Data Bits/Length 8
Parity None
Stop bits 1
Address/Device ID 88, 1-9
Trouble-Shooting
Problem: Not getting a response from the
gateway device
 Ensure the connection is set to 9600 8-N-1
 Check the rotary dial switch for the device
addressing and it not in between dial
settings
 Ensure the communication cables match
their polarity