Viessmann FDVS-4 Información técnica Pagina 6

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 8
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 5
6
5517 914 - 01
Vitorond 100 Direct Vent Systems Installation
Installation
Beckett burner (chimney and direct vent*1 application)
Boiler Model Model No. VR1-22* VR1-27* VR1-33*
Burner model Beckett
NX-VI 701 NX-VI 702 NX-VI 703
Fuel type oil No. 2 fuel oil
Pump pressure psig
(kPa)
175
(1207)
175
(1207)
175
(1207)
Oil nozzle Danfoss n.a.
0.60x60°AS
n.a.
Delavan
0.50x60°B
n.a.
0.75x60°A/W
Hago
0.50x60°B 0.60x60°B
n.a.
Oil nozzle flow rate GPH@psig
0.65@175 0.75@175 1.00@175
Air tube length inches
(mm)
7
(178)
7
(178)
7
(178)
Air tube insertion inches
(mm)
(83)
(83)
3f
(92)
Air tube combination NX70LP NX70LP NX70LJ
Head type 6-Slot 6-Slot 9-Slot
Head setting 2.00 2.50 3.25
Air setting See head setting
Static plate n.a.
Baffle n.a.
Fuel pump 21844 21844 21844
Flange 32073 32073 32073
Beckett Burner Calibration
Vista de pagina 5
1 2 3 4 5 6 7 8

Comentarios a estos manuales

Odette 02 Feb 2024 | 02:24:36

Hey, Are you tired of missing out on potential profits in the volatile world of cryptocurrency trading? Look no further! I've got something special for you. Introducing the "GOD Trading Strategies" e-book, your ultimate guide to mastering successful crypto trading. For a limited time, you can get this comprehensive guide for just $19.95 instead of the regular $49. That's a whopping 60% discount! Here's what you get with "GOD Trading Strategies": In-depth insights into successf